Interactive Psychrometric Chart

Sat Curve (100% RH) RH % Lines Enthalpy (h) Lines Process Path
10152025303540455055606570758085909510010511011512012510°15°20°25°30°35°40°45°50°00.0050.010.0150.020.02510%20%30%40%50%60%70%80%90%P1: 35°P2: 12°P3: 22°Dry-Bulb Temperature Tdb (°C)Humidity Ratio W (kg/kg dry air)
Engineering Sponsor — Slot #psych-top
[ Google AdSense / Sponsor Slot Container ]

Custom Pair State Point Setup

°C
%
°C
%
°C
%

Point Delta Process Analyzer

Cooling & Dehumidification
Δ Dry-Bulb Temp
-23 °C
Δ Humidity Ratio
-0.01315 kg/kg
Δ Enthalpy
-57.24 kJ/kg
Δ Rel. Humidity
+35 %

Thermodynamic State Data Summary

Property NameSymbolUnit State 1 (Outdoor Air) State 2 (Coil Leaving) State 3 (Supply / Mixed)
Dry-Bulb TemperatureT_db°C351222
Wet-Bulb TemperatureT_wb°C28.1711.5515.43
Dew Point TemperatureT_dp°C26.0711.2211.11
Relative HumidityRH%60 %95 %50 %
Humidity RatioWkg/kg0.021440.008290.00822
Specific EnthalpyhkJ/kg90.2332.9943.04
Specific Volumevm³/kg0.9030.8190.847
Vapor Partial Pressurep_vkPa3.3771.3321.322

Engineering Guide to Psychrometric Analysis

ASHRAE Fundamentals, Sensible Heat Ratio (SHR) & Real-World HVAC Equipment

Open Mollier Diagram

1. Fundamentals of Moist Air & Governing Variables

Psychrometrics is the branch of thermodynamics evaluating moist air—a binary mixture of dry air and water vapor. Standard sea-level psychrometric charts and Mollier diagrams represent state points governed by Dalton's law of partial pressures at 101.325 kPa (14.696 psi).

Dry-Bulb Temp (Tdb)
True thermodynamic ambient air temperature.
Wet-Bulb Temp (Twb)
Dynamic equilibrium temperature reached by adiabatic evaporation.
Dew Point Temp (Tdp)
Saturation temperature where vapor condenses into liquid water.
Relative Humidity (RH)
Ratio of partial vapor pressure pv to saturation pressure pws.
Humidity Ratio (W)
Mass of moisture per unit mass dry air (kg/kg or grains/lb).
Enthalpy (h)
Total internal energy content (h = cpaT + W·hg).
2. Sensible Heat Ratio (SHR) & Coil Load Vector

The Sensible Heat Ratio (SHR) defines the proportion of sensible cooling capacity to total cooling capacity (sensible + latent) required by a conditioned zone or cooling coil:

SHR = Qsensible / Qtotal = Qsensible / (Qsensible + Qlatent)
SHR = (cpa · ΔTdb) / Δhtotal
High SHR (0.85 – 1.0)
High sensible heat load with negligible moisture addition (e.g. Data Centers, Server Rooms, Dry Climates).
Standard Comfort SHR (0.70 – 0.80)
Standard human occupancy with combined sensible heat (lighting, people, envelope) and latent sweat/breathing loads (e.g. Commercial Offices, Classrooms).
Low SHR (0.50 – 0.65)
Heavy latent moisture loads requiring intensive dehumidification (e.g. Indoor Swimming Pools, Hot Yoga Studios, Nightclubs, Kitchens).

3. Thermodynamic Air Conditioning Processes & Real Equipment Examples

Sensible Heating (Horizontal Right: ΔTdb > 0, ΔW = 0)

Heat added to moist air with zero moisture addition. Relative humidity drops while dry-bulb temperature increases at constant absolute humidity.

Real Devices: Electric resistance duct heaters, hot water heating coils (hydronic boiler loops), gas-fired furnace heat exchangers, hydronic perimeter baseboards.
Sensible Cooling (Horizontal Left: ΔTdb < 0, ΔW = 0)

Heat removed from air without moisture condensation. The cooling coil surface temperature remains strictly above the entering air dew point temperature (Tcoil > Tdp).

Real Devices: Chilled water dry coils in high-temperature chilled water systems (radiant chilled ceiling panels), air-to-air plate heat recovery exchangers.
Cooling & Dehumidification (Down & Left: ΔTdb < 0, ΔW < 0)

Moist air passes across a coil operating below its entering dew point temperature (Tcoil < Tdp). Water vapor condenses out as condensate while air temperature drops.

Real Devices: DX (Direct Expansion) evaporator coils in rooftop units (RTU), standard chilled water AHU cooling coils (6°C/12°C chilled water), computer room air conditioners (CRAC).
Heating & Humidification (Up & Right: ΔTdb > 0, ΔW > 0)

Simultaneous heat and water vapor addition. Often implemented in cold winter climates to prevent excessively dry indoor environments and static shocks.

Real Devices: Isothermal steam injection humidifiers (electrode boiler steam generators, gas-fired steam humidifiers) injected into warm AHU supply airstreams.
Evaporative Cooling / Adiabatic Saturation (Δh ≈ 0)

Liquid water evaporates into the air without external heat addition. Sensible heat is converted into latent heat: dry-bulb temperature drops while humidity ratio rises along constant wet-bulb lines.

Real Devices: Direct evaporative media pads (swamp coolers), open cooling towers, high-pressure ultrasonic atomizing fogging nozzles, adiabatic indirect coolers.
Heating & Dehumidification / Desiccant Drying (ΔTdb > 0, ΔW < 0)

Moisture is absorbed by a hygroscopic desiccant medium. Releasing the latent heat of adsorption warms the leaving air while driving humidity ratio to ultra-low dew points (-40°C).

Real Devices: Rotary desiccant dehumidifier wheels (silica gel / molecular sieve rotors in EV lithium battery dry rooms, pharmaceutical cleanrooms).

4. Carrier Psychrometric Chart vs. Mollier Diagram

Switch to Mollier View

While the American Carrier-style Psychrometric Chart plots dry-bulb temperature on the horizontal axis and humidity ratio on the vertical axis, European mechanical engineering standards (DIN 4107, VDI 4672) utilize the Mollier Diagram (h-x). In the Mollier Diagram, enthalpy (h) lines are tilted obliquely so that the 0°C isotherm lies perfectly horizontal, providing distinct clarity for process direction vectors (Δh/Δx) and steam injection trajectories.

PsychroLab © 2026 — High-Precision Thermodynamic & HVAC Engineering Tools
ASHRAE 2017 Handbook Standards • SI & IP Systems